Digital Pneumatic Valve Positioner Two wire 4mA 3200md

Place of Origin USD
Certification CCC.CE
Model Number 3200MD
Minimum Order Quantity 1
Price usd$2800 /pc
Packaging Details carton
Delivery Time 5-10 Work days
Payment Terms L/C, D/A, D/P, T/T, Western Union, MoneyGram
Supply Ability 100

Contact me for free samples and coupons.

Whatsapp:0086 18588475571

Wechat: 0086 18588475571

Skype: sales10@aixton.com

If you have any concern, we provide 24-hour online help.

x
Product Details
Brand Name Flowserve Model 3200Md-10-d6-e-04-40-0g-0f
Color White Application General
High Light

Two Wire Pneumatic Valve Positioner

,

Digital Control Valve With Positioner

,

3200md Pneumatic Control Valve Positioner

You can tick the products you need and communicate with us in the message board.
Power Supply Two-wire, 4-20 mA 10.0 to 30.0 VDC
Communications HART Protocol
Maximum Voltage 30.0 VDC
Transport and Storage Temperature Range -40° to 176°F (-40° to 80°C)
Leave a Message
Power Supply Two-wire, 4-20 mA 10.0 to 30.0 VDC
Product Description

New and Original 4-20 mA Digital Valve Positioner Flowserve Logix 3200md pneumatic valve positioner

 

The Logix 3200MD digital positioner is a two-wire 4-20 mA input digital valve positioner. The positioner is configurable through the local user interface. The Logix 3200MD utilizes the HART protocol to allow two-way remote communications with the positioner. The Logix 3200MD positioner can control both double- and single-acting actuators with linear or rotary mountings. The positioner is completely powered by the 4-20 mA input signal. Start up current must be at least 3.6 mA without AO card or 3.85 mA with AO card.

 

The Foss Logix 3200MD Digital HART positioner utilizes piezoelectric technology to provide superior performance and reliability. The Logix 3200MD can be easily configured using native buttons, HART handhelds and SoftTools s

Digital Pneumatic Valve Positioner Two wire 4mA 3200md 0

Features and Benefits

  • Local status LED's
  • Local DIP Switches/Calibration Buttons
  • Auto Tuning with dynamic gain selection
  • Utilizes HART 5
  • Simple calibration via local interface
  • Explosion proof enclosure rated Class I Division 1 Groups B-D, Ex d IIB+H2, AEx d IIB+H2
  • Intrinsically Safe Rated Class I, Div 1, Groups A-G, Ex ia IIC, AEx ia IIC
  • Non-Incendive Class I Div 2 A-D, Ex nA
  • SIL 2

Specifications

Brand Name Flowserve
Model 3200Md-10-d6-e-04-40-0g-0f
Power Supply Two-wire, 4-20 mA 10.0 to 30.0 VDC
Compliance Voltage 10.0 VDC @ 20 mA
Communications HART Protocol
Transport and Storage Temperature Range -40° to 176°F (-40° to 80°C)

 

Digital Pneumatic Valve Positioner Two wire 4mA 3200md 1

 

 

Digital Pneumatic Valve Positioner Two wire 4mA 3200md 2The Logix 3200MD positioner is an electric feedback instrument. Figure 1 shows a Logix 3200MD positioner installed on a double-acting linear actuator for air-to-open action. The Logix 3200MD receives power from the two-wire, 4-20 mA input signal. However, since this positioner utilizes HART communications, two sources can be used for the command signal: Analog and Digital. In Analog source, the 4-20 mA signal is used for the command source. In Digital source, the level of the input 4-20 mA signal is ignored and a digital signal, sent via HART, is used as the command source. The command source can be accessed with ValveSight software, the HART 375 communicator, or other host software. Whether in Analog or Digital Source, 0% is always defined as the valve closed position and 100% is always defined as the valve open position. In Analog Source, the 4-20 mA signal is converted to a percentage. During loop calibration, the signals corresponding to 0% and 100% are defined.

Digital Pneumatic Valve Positioner Two wire 4mA 3200md 3

A more detailed example explains the control function. Assume the unit is configured as follows:

• Unit is in Analog command source.

• Custom characterization is disabled (therefore characterization is Linear).

• No soft limits enabled. No MPC set.

• Valve has zero deviation with a present input signal of 12 mA.

• Loop calibration: 4 mA = 0% command, 20 mA = 100% command.

• Actuator is tubed and positioner is configured air-to-open

 

 

Note: The air supply must conform to ISA Standard ISA 7.0.01 (a dew point at least 18 degrees Fahrenheit below ambient temperature, particle size below five microns—one micron recommended—and oil content not to exceed one part per million).