Fluke 1555 FC 10 kV Insulation Tester with High Accuracy Insulation Resistance Measurement

Place of Origin China
Brand Name FLUKE
Model Number 1555 FC
Minimum Order Quantity 2
Price USD$299
Packaging Details Original packaging
Delivery Time in stock
Payment Terms L/C, D/A, D/P, T/T, Western Union
Supply Ability 10PC
Product Details
Highlight

Fluke 1555 FC insulation tester

,

10 kV insulation tester

,

original Fluke voltage meter

Leave a Message
Product Description
Electrical Specifications
The tester's accuracy is specified for one year after calibration at operating temperatures of 0°C to 35°C. For operating temperatures outside the range (-20°C to 0°C and 35°C to 50°C), add ±.25% per °C, except on the 20% bands add ±1% per °C.
Insulation Resistance Measurement
Test voltage (DC)
250 V Range < 250 kΩ,
250 kΩ to 5 GΩ
5 GΩ to 50 GΩ
> 50 GΩ
Accuracy (± reading) Unspecified
5%
20%
Unspecified
500 V Range < 500 kΩ
500 kΩ to 10 GΩ
10 GΩ to 100 GΩ
> 100 GΩ
Accuracy (± reading) Unspecified
5%
20%
Unspecified
1000 V Range < 1 MΩ
1 MΩ to 20 GΩ
20 GΩ to 200 GΩ
> 200 GΩ
Accuracy (± reading) Unspecified
5%
20%
Unspecified
2500 V Range < 2.5 MΩ
2.5 MΩ to 50 GΩ
50 GΩ to 500 GΩ
> 500 GΩ
Accuracy (± reading) Unspecified
5%
20%
Unspecified
5000 V Range < 5 MΩ
5 MΩ to 100 GΩ
100 GΩ to 1 TΩ
> 1 TΩ
Accuracy (± reading) Unspecified
5%
20%
Unspecified
10000 V Range < 10 MΩ
10 MΩ to 200 GΩ
200 GΩ to 2 TΩ
> 2 TΩ
Accuracy (± reading) Unspecified
5%
20%
Unspecified
Bar graph range 0 to 1 TΩ (1550C) - 0 to 2 TΩ (1555)
Insulation test voltage accuracy -0%, +10% at 1 mA load current
Induced AC mains current rejection 2 mA maximum
Charging rate for capacitive load 5 seconds per μF
Discharge rate for capacitive load 1.5 s/μF
Leakage current measurement Range 1 nA to 2 mA
Accuracy ±(5% + 2 nA)
Capacitance measurement Range 0.01 μF to 15.00 μF
Accuracy ±(15% rdg + 0.03 μF)
Timer Range 0 to 99 minutes
Resolution setting 1 minute
Resolution indication 1 second
Live circuit warning Warning range 30 V to 660 V AC/DC, 50/60 Hz
Voltage accuracy ±(15% + 2 V)